Customization: | Available |
---|---|
Application Fields: | Industrial Gas Burner |
Certification: | ISO, CE |
Still deciding? Get samples of US$ 94/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The Honeywell RM7840L1018 Burner Control 120V, 50/60 HZ. AirFlow Switch CHECK OPTION. INCLUDES DUST Cover.
* Flame Establishing Period - Pilot, 4 sec or 10 sec
* Flame Establishing Period - Main, 10 sec or 15 sec
* Early Spark Termination - Yes, 5 sec
* Required Components: Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card
item
|
value
|
Condition
|
New
|
Warranty
|
1.5 years
|
Applicable Industries
|
Manufacturing Plant, Food & Beverage Factory, Farms, Restaurant, Construction works , Energy & Mining, Advertising Company
|
Weight (KG)
|
2
|
Showroom Location
|
None
|
Video outgoing-inspection
|
Provided
|
Machinery Test Report
|
Provided
|
Place of Origin
|
China
|
Brand Name
|
JATE
|
Type
|
Gas Burner
|
Product name
|
Industrial High Performance Controller TBC2800A1000 |
Brand
|
JATE
|
Model
|
TBC2800A1000 |
Color
|
Blue
|
Size
|
L*W*H: 122 X 82 X 130.8 mm
|
Input voltage
|
220/230 VAC -15/+10%, 50/60Hz
|
Maximum power
|
9 VA
|
Ion bar cable length
|
75m (longest)
|
UV cable length
|
75m (the longest)
|
Flame Threshold Initial Setting
|
1µA (minimum)
|
Shell material
|
PC/ABS black (base) blue (case)
|
Protection class
|
IP54
|
Ambient temperature
|
-20ºC~+60ºC
|
Ambient humidity
|
< 95%
|
Operating life
|
250,000 times (according to EN298 standard)
|
The maximum current to drive the gas valve
|
1A; power factor: 1
|
Maximum current to drive ignition transformer
|
2A; power factor: 0.2
|
Maximum current of output terminal
|
2A; AC voltage: 242V
|
UV fire detection sensor model
|
C7027A / C7035A / C7044A
|
Features:
China Brand JAT TBC2800 Series Gas Burner Parts Controller Industrial High Performance Controller TBC2800A1000